Title 18 - Unified Development Ordinance
18.435 Outdoor Lighting
18.435.030 Lighting Plan Requirements
-
A.For new construction, the lighting plan shall be included as part of the Final Development Plan or Site Plan approval required in 18.140.220 or 18.140.180.
-
B.For replacement lighting, the lighting plan shall be submitted with the building permit, if a building permit is required. If no building permit is required all lighting shall meet the requirements of this Chapter. The Director may approve a lighting plan that meets the requirements of this Chapter, to the maximum amount feasible.
-
C.All lighting plans shall be prepared by a certified lighting designer or professional engineer to include the following information:
-
1.North arrow and scale.
-
2.The location, size and surface of materials of all structures and parking areas.
-
3.The location, size, type and quantity of all proposed exterior fixtures and light poles.
-
4.
Cut Sheets for each light fixture with highlights on the exact model attributes.
-
5.
A point-by-point calculation using a five foot grid to show compliance with the lighting standards.
-
a.The horizontal calculations shall be measured at 5 feet above grade for lighting levels within the development site.
-
-
6.A development table containing average maintained footcandles, average to minimum, and maximum to minimum uniformity ratios.
-
7.A vertical plan footcandle calculation at 5-foot intervals at 5 feet above grade for property lines abutting residential properties.
-
8.If required by the Director, topographic information and final grading adequate to identify any unique situations that could affect parking lot lighting.
-
(History: Ord. No. ZRR-3447 §4, 2024)