Title 16 - Buildings and Construction
16.110 Residential Code for One- & Two-Family Dwellings
16.110.R302.13
Section R302.13 of the International Residential Code for One- and Two-Family Dwellings is hereby amended to read as follows:
R302.13 Fire Protection of Floors
Floor assemblies that are not required elsewhere in this code to be fire-resistance rated, shall be provided with a ½-inch gypsum wallboard membrane, ⅝-inch wood structural panel membrane, or equivalent on the underside of the floor framing member. Penetrations or openings for ducts, vents, electrical outlets, lighting, devices, luminaires, wires, speakers, drainage, piping and similar openings or penetrations shall be permitted.
Exceptions:
- 1.Floor assemblies located directly over a space protected by automatic fire sprinklers. The sprinklers are permitted to be installed on a ¾-inch domestic water line.
- 2.Floor assemblies located directly over a crawl space.
- 3.Portions of floor assemblies shall be permitted to be unprotected where complying with the following:
3.1. The aggregate area of the unprotected portions does not exceed 80 square feet per story.
3.2. Fireblocking in accordance with Section R302.11.1 is installed along the perimeter of the unprotected portion from the remainder of the floor assembly.
- 4.Wood floor assemblies using dimension lumber or structural composite lumber equal to or greater than 2-inch by 10-inch nominal dimension, or other approved floor assemblies demonstrating equivalent fire performance.
(History: Ord. BC-3286 §52, 2020)